2x2/0+2/0 AWG

Description

Description

Standards

  • Product
    ASTM B 232; ICEA S-76-474
  • National
    NTC 309; NTC 5346

Applications

SELF SUPPORTED MULTIPLEX CABLES Centelsa by Nexans are used in aerial secondary distribution systems, in public lighting or in temporary construction installations, connection with the transformer to the point of derivation for the user or connection with the distribution box.

Construction

Phase Conductor

Aluminum 1350-H19 hard tempering, concentric stranded.

Neutral Conductor

Aluminum support conductor with Steel Core (ACSR), concentric stranded.

Insulation

Composed of cross-linked polyethylene XLPE, resistant to UV rays.

Applicable standards

  • NTC 5346, ICEA S-76-474.
  • NTC 4334, ASTM B-400.
  • NTC 309, ASTM B-232.

Certificate

CIDET N° 02619/01336

Operating Temperature

90°C

Operating Voltage

600 V

Identification

• Phase conductors identification by polarity ridges.

 

Packaging units

Wooden reels in 500 o 1000 m.

Opcional

  • Bare Neutral conductor.
  • Flame retardant insulation.
  • Neutral conductor type AAAC or AAC.
  • Identification in color traces.

Ampacity Conditions (Self Supported Multiplex Cables)

  • Ampacity to 90°C conductor temperature, 40°C ambient temperature.
  • No more than three individual insulated and self-supported conductors per messenger according to NTC 2050, Table 310.15(B)(20).

NOTE:

  • The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Phase Conductor Type
AAC - All Aluminium Conductor
Conductor material
Aluminum Alloy 1350
Conductor flexibility
Class B
Conductor shape
Compact stranded
Neutral Type
ACSR - Aluminium Conductor Steel Reinforced
Insulation
XLPE

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
67.4 mm²
Number of cores
3
Phase Conductor Conductor cross-section (AWG)
2/0 AWG
Conductor diameter
9.55 mm
Nominal insulation thickness
1.52 mm
Neutral Conductor cross-section (AWG)
2/0 AWG
Neutral Conductor Diameter
11.01 mm
Insulation thickness of neutral conductor
1.52 mm
Approximate weight
840.32 kg/km
Nominal outer diameter
29.02 mm

Electrical characteristics

Electrical characteristics

Ampacity
193.0 A
Max. DC resistance of the conductor at 20°C
0.437 Ohm/km
Operating voltage
600 V

Mechanical characteristics

Mechanical characteristics

Rated breaking load
2406 kgf

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C
U.V resistance
ICEA S-76-474 - Sunlight Resistance
RoHS compliant
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close