NA2XSY 20/35 kV PH+PC; ABNT NBR 6251; ABNT NBR 7286; Comp. Anti-roedor

Productos

NA2XSY 20/35 kV 240 mm2 PH16

Nexans ref. P00034148-0

  • Sección del conductor: 240 mm²
  • Diámetro del conductor: 18,0 mm
  • Diámetro sobre aislamiento: 37,1 mm
  • Diameter over screen: 40,5 mm
  • Diámetro sobre la chaqueta: 45,5 mm
  • Peso aproximado: 2115 kg/km

 

NA2XSY 20/35 kV 300 mm2 PH16

Nexans ref. P00034149-0

  • Sección del conductor: 300 mm²
  • Diámetro del conductor: 20,4 mm
  • Diámetro sobre aislamiento: 39,5 mm
  • Diameter over screen: 42,8 mm
  • Diámetro sobre la chaqueta: 48 mm
  • Peso aproximado: 2385 kg/km

 

NA2XSY 20/35 kV 400 mm2 PH16

Nexans ref. P00034150-0

  • Sección del conductor: 400 mm²
  • Diámetro del conductor: 23,1 mm
  • Diámetro sobre aislamiento: 42,2 mm
  • Diameter over screen: 45,5 mm
  • Diámetro sobre la chaqueta: 50,9 mm
  • Peso aproximado: 2757 kg/km

 

NA2XSY 20/35 kV 500 mm2 PH16

Nexans ref. P00034151-0

  • Sección del conductor: 500 mm²
  • Diámetro del conductor: 26,2 mm
  • Diámetro sobre aislamiento: 45,3 mm
  • Diameter over screen: 48,7 mm
  • Diámetro sobre la chaqueta: 54,3 mm
  • Peso aproximado: 3220 kg/km

 

NA2XSY 20/35 kV 630 mm2 PH16

Nexans ref. P00034152-0

  • Sección del conductor: 630 mm²
  • Diámetro del conductor: 29,8 mm
  • Diámetro sobre aislamiento: 48,9 mm
  • Diameter over screen: 52,3 mm
  • Diámetro sobre la chaqueta: 58 mm
  • Peso aproximado: 3775 kg/km

 

Descripción

Descripción

Estándares

  • Producto
    ABNT NBR 6251 ; ABNT NBR 7287 ; ICEA S-93-639; IEC 60228; NTP-IEC 60228
  • Ensayo
    IEC 60332-1-2; IEC 60811-401; IEC 60811-402; IEC 60811-409; IEC 60811-501; IEC 60811-502; IEC 60811-504; IEC 60811-505; IEC 60811-506; IEC 60811-507; IEC 60811-508; IEC 60811-509; UL 2556

Applications

Power distribution in medium voltage. In power plants and electrical substations, industrial and operation installations, in residential areas and mining installations, in dry or wet locations.

Construction

1. Conductor: Compact round aluminium 1350, class 2.
2. Inner semi-conductor: Extruded.
3. Insulation: Cross linked polyethylene XLPE-TR (Tree retardant).
4. External semi-conductor: Extruded strippable.
These last three components extruded CV (continuous vulcanization) triple extrusion in dry cure process.

5. Screen: Copper wires + copper tape in open helix.
6. Tape: Polyester tape.
7. Outer sheath: Compound polyvinyl chloride PVC with antirodent compound.

Main characteristics

Excellent properties against heat aging. Resistance to abrasion, moisture and sunlight. Adequate resistance to greases and oils. Flame retardant. Resistance to attack by rodents.

Cross section:
From 240 mm2 up to 630 mm2.

Packing:
Non returnable wooden reels.

Colour:
Insulation: Natural.

Outer sheath: Black.

Standards

National standards

NTP-IEC 60228: Conductors of insulated cables.

International standards

IEC 60228: Conductors of insulated cables.

ABNT NBR 6251: Insulated power cables, for rated voltages 1 kV up to 35 kV - Constructive requirements.

ABNT NBR 7287: Power cables extruded cross-linked polyethylene insulated power cable for rated voltages from 1 up to 35 kV - Performace requirements.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3:FT1 (Vertical-Specimen) Flame Test.

IEC 60811-401: Thermal ageing methods. Ageing in an air oven.

IEC 60811-402: Water absorption tests.

IEC 60811-409: Loss of mass test for thermoplastic insulations and sheaths.

IEC 60811-501: Test for determining the mechanical properties.

IEC 60811-502: Shrinkage test for insulations.

IEC 60811-504: Bending test at low temperature for insulation and sheaths.

IEC 60811-505: Elongation at low temperature for insulations and sheaths.

IEC 60811-506: Impact test at low temperature for insulations and sheaths.

IEC 60811-507: Hot set test for cross-linked materials.

IEC 60811-508: Pressure test at high temperature for insulation and sheaths.

IEC 60811-509: Test for resistance of insulations and sheaths to cracking.

ICEA S-93-639: 5-46 kV Shielded Power Cable for Use in the Transmission and Distribution of Electric Energy. Section 9.4.2: Oil Immersion Test.

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.

BENDING RADIUS INSTALLED IN M.V

R=Dxf

R:  Bending radius when installed (mm)

D:  Diameter over sheath (mm)

f:   Multiplicative factor; given the following table:

 

Bending radius factor MV

Calculation of Current Condition Single core Medium Voltage

CALCULATION OF CURRENT CONDITION BASED ON ABNT NBR 14039

Maximum conductor temperature: 90°C.
Ambient air temperature: 30°C.
Ground temperature: 20°C.
Depth of laying: 0,9 m.
Thermal resistivity of soil: 1,5 K.m/W.

Características

Características

Características de construcción

Características de construcción

Material del conductor
Aluminum Alloy 1350
Material of the inner semi-conductor
Extruded
Material de aislamiento
XLPE-TR
Material of the external semi-conductor
Extruded strippable
Pantalla
Cinta e Hilos de Cobre
Cubierta Exterior
PVC
Color de cubierta
Black - UV
Libre de plomo
Yes

Características dimensionales

Características dimensionales

Screen section
16 mm²

Características eléctricas

Características eléctricas

Tensión nominal de servicio Uo/U
20/35 kV
Impulse voltage
200 kV

Características mecánicas

Características mecánicas

Flexibilidad del cable
Class 2 IEC 60228

Características de uso

Características de uso

Resistencia a radiaciones ultravioletas
UL 2556 - Sunlight Resistance
Resistencia a aceites
ICEA S-93-639
No propagación de la llama
IEC 60332-1-2; FT1
Protección Anti roedores
Cubierta Anti roedores
Temperatura máxima operativa
90 °C
Temperatura de sobrecarga de emergencia
130 °C
Temperatura máxima del conductor en corto-circuito
250 °C

Recursos

Recursos

Selling & delivery Information

Marking:
INDECO S.A. NA2XSY 20/35 kV - Cross section - PH(Screen section) - Year - Sequential length.

Contáctanos

Temas sobre los que desea recibir mayor información

Campos requeridos

Por favor revise la data ingresada e intente nuevamente

El correo debe contener este símbolo @

Protección de data personal

Tiene el derecho de rechazar el procesamiento de sus datos personales y/o su uso para propósitos comerciales

¡Gracias!

Gracias por contactarse con nosotros. Nos pondremos en contacto pronto.

Error

Ocurrió un error. Por favor intentar nuevamente

Cerrar

Contáctanos

Campos requeridos

Por favor revise la data ingresada e intente nuevamente

El correo debe contener este símbolo @

Protección de data personal

Tiene el derecho de rechazar el procesamiento de sus datos personales y/o su uso para propósitos comerciales

¡Gracias!

Gracias por contactarse con nosotros. Nos pondremos en contacto pronto.

Error

Ocurrió un error. Por favor intentar nuevamente

Cerrar