MULTICONDUCTOR POWER CABLE (AS+) FIRE RESISTANT 0.6/1kV
MULTICONDUCTOR POWER CABLE (AS+) FIRE RESISTANT 0.6/1kV
Secondary distribution in low voltage. Indoor installations of industrial, commercial and residential buildings that must continue to operate in case of exposure to fire.
Read more5x2,5mm2
Nexans ref.
- Conductor cross-section: 2.5 mm²
- Outer Diameter: 13.47 mm
- Approximate weight: 259.8 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
- Ampacity: 28.0 A
2x2,5mm2
Nexans ref.
- Conductor cross-section: 2.5 mm²
- Outer Diameter: 10.72 mm
- Approximate weight: 153.88 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
- Ampacity: 28.0 A
3x2,5mm2
Nexans ref.
- Conductor cross-section: 2.5 mm²
- Outer Diameter: 11.33 mm
- Approximate weight: 179.98 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
- Ampacity: 28.0 A
4x2,5mm2
Nexans ref.
- Conductor cross-section: 2.5 mm²
- Outer Diameter: 12.34 mm
- Approximate weight: 215.15 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
- Ampacity: 28.0 A
5x4mm2
Nexans ref. 10040777
- Conductor cross-section: 4 mm²
- Outer Diameter: 14.95 mm
- Approximate weight: 356.59 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
- Ampacity: 36.0 A
2x4mm2
Nexans ref.
- Conductor cross-section: 4 mm²
- Outer Diameter: 11.82 mm
- Approximate weight: 200.25 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
- Ampacity: 36.0 A
3x4mm2
Nexans ref.
- Conductor cross-section: 4 mm²
- Outer Diameter: 12.51 mm
- Approximate weight: 239.11 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
- Ampacity: 36.0 A
4x4mm2
Nexans ref.
- Conductor cross-section: 4 mm²
- Outer Diameter: 13.67 mm
- Approximate weight: 289.45 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
- Ampacity: 36.0 A
5x6mm2
Nexans ref. 10040447
- Conductor cross-section: 6 mm²
- Outer Diameter: 16.52 mm
- Approximate weight: 465.46 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
- Ampacity: 44.0 A
2x6mm2
Nexans ref.
- Conductor cross-section: 6 mm²
- Outer Diameter: 12.98 mm
- Approximate weight: 255.74 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
- Ampacity: 44.0 A
3x6mm2
Nexans ref.
- Conductor cross-section: 6 mm²
- Outer Diameter: 13.76 mm
- Approximate weight: 310.36 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
- Ampacity: 44.0 A
4x6mm2
Nexans ref.
- Conductor cross-section: 6 mm²
- Outer Diameter: 15.07 mm
- Approximate weight: 379.16 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
- Ampacity: 44.0 A
5x10mm2
Nexans ref. 10040448
- Conductor cross-section: 10 mm²
- Outer Diameter: 19.19 mm
- Approximate weight: 704.09 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Ampacity: 58.0 A
2x10mm2
Nexans ref.
- Conductor cross-section: 10 mm²
- Outer Diameter: 14.96 mm
- Approximate weight: 370.32 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Ampacity: 58.0 A
3x10mm2
Nexans ref.
- Conductor cross-section: 10 mm²
- Outer Diameter: 15.9 mm
- Approximate weight: 459.34 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Ampacity: 58.0 A
4x10mm2
Nexans ref.
- Conductor cross-section: 10 mm²
- Outer Diameter: 17.46 mm
- Approximate weight: 567.73 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Ampacity: 58.0 A
5x16mm2
Nexans ref. 10040449
- Conductor cross-section: 16 mm²
- Outer Diameter: 21.6 mm
- Approximate weight: 1002.93 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
- Ampacity: 75.0 A
2x16mm2
Nexans ref.
- Conductor cross-section: 16 mm²
- Outer Diameter: 16.74 mm
- Approximate weight: 512.9 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
- Ampacity: 75.0 A
3x16mm2
Nexans ref.
- Conductor cross-section: 16 mm²
- Outer Diameter: 17.81 mm
- Approximate weight: 649.86 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
- Ampacity: 75.0 A
4x16mm2
Nexans ref.
- Conductor cross-section: 16 mm²
- Outer Diameter: 19.61 mm
- Approximate weight: 811.77 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.7 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
- Ampacity: 75.0 A
2x25mm2
Nexans ref.
- Conductor cross-section: 25 mm²
- Outer Diameter: 20.08 mm
- Approximate weight: 758.82 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
- Ampacity: 96.0 A
3x25mm2
Nexans ref.
- Conductor cross-section: 25 mm²
- Outer Diameter: 21.41 mm
- Approximate weight: 968.23 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
- Ampacity: 96.0 A
4x25mm2
Nexans ref.
- Conductor cross-section: 25 mm²
- Outer Diameter: 23.64 mm
- Approximate weight: 1214.6 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
- Ampacity: 96.0 A
5x25mm2
Nexans ref.
- Conductor cross-section: 25 mm²
- Outer Diameter: 26.11 mm
- Approximate weight: 1511.58 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
- Ampacity: 96.0 A
2x35mm2
Nexans ref.
- Conductor cross-section: 35 mm²
- Outer Diameter: 22.42 mm
- Approximate weight: 1001.1 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
- Ampacity: 115.0 A
3x35mm2
Nexans ref.
- Conductor cross-section: 35 mm²
- Outer Diameter: 23.93 mm
- Approximate weight: 1290.95 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
- Ampacity: 115.0 A
4x35mm2
Nexans ref.
- Conductor cross-section: 35 mm²
- Outer Diameter: 26.47 mm
- Approximate weight: 1627.65 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
- Ampacity: 115.0 A
5x35mm2
Nexans ref.
- Conductor cross-section: 35 mm²
- Outer Diameter: 29.27 mm
- Approximate weight: 2029.34 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 0.9 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
- Ampacity: 115.0 A
2x50mm2
Nexans ref.
- Conductor cross-section: 50 mm²
- Outer Diameter: 25.82 mm
- Approximate weight: 1376.63 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 1.0 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
- Ampacity: 135.0 A
3x50mm2
Nexans ref.
- Conductor cross-section: 50 mm²
- Outer Diameter: 27.6 mm
- Approximate weight: 1787.38 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 1.0 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
- Ampacity: 135.0 A
4x50mm2
Nexans ref.
- Conductor cross-section: 50 mm²
- Outer Diameter: 30.57 mm
- Approximate weight: 2261.21 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 1.0 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
- Ampacity: 135.0 A
5x50mm2
Nexans ref.
- Conductor cross-section: 50 mm²
- Outer Diameter: 34.02 mm
- Approximate weight: 2836.66 kg/km
- Minimum outer sheath thickness: 1.32 mm
- Nominal insulation thickness: 1.0 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
- Ampacity: 135.0 A
2x70mm2
Nexans ref.
- Conductor cross-section: 70 mm²
- Outer Diameter: 29.76 mm
- Approximate weight: 1885.19 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
- Ampacity: 167.0 A
3x70mm2
Nexans ref.
- Conductor cross-section: 70 mm²
- Outer Diameter: 32 mm
- Approximate weight: 2472.7 kg/km
- Minimum outer sheath thickness: 1.32 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
- Ampacity: 167.0 A
4x70mm2
Nexans ref.
- Conductor cross-section: 70 mm²
- Outer Diameter: 35.65 mm
- Approximate weight: 3147.95 kg/km
- Minimum outer sheath thickness: 1.4 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
- Ampacity: 167.0 A
5x70mm2
Nexans ref.
- Conductor cross-section: 70 mm²
- Outer Diameter: 39.66 mm
- Approximate weight: 3948.31 kg/km
- Minimum outer sheath thickness: 1.48 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
- Ampacity: 167.0 A
2x95mm2
Nexans ref.
- Conductor cross-section: 95 mm²
- Outer Diameter: 34.3 mm
- Approximate weight: 2487.88 kg/km
- Minimum outer sheath thickness: 1.32 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Ampacity: 197.0 A
3x95mm2
Nexans ref.
- Conductor cross-section: 95 mm²
- Outer Diameter: 36.88 mm
- Approximate weight: 3259.69 kg/km
- Minimum outer sheath thickness: 1.4 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Ampacity: 197.0 A
4x95mm2
Nexans ref.
- Conductor cross-section: 95 mm²
- Outer Diameter: 41.09 mm
- Approximate weight: 4148.42 kg/km
- Minimum outer sheath thickness: 1.48 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Ampacity: 197.0 A
5x95mm2
Nexans ref.
- Conductor cross-section: 95 mm²
- Outer Diameter: 48.82 mm
- Approximate weight: 5534.79 kg/km
- Minimum outer sheath thickness: 1.64 mm
- Nominal insulation thickness: 1.1 mm
- Number of cores: 5
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Ampacity: 197.0 A
2x120mm2
Nexans ref.
- Conductor cross-section: 120 mm²
- Outer Diameter: 38.5 mm
- Approximate weight: 3132.58 kg/km
- Minimum outer sheath thickness: 1.4 mm
- Nominal insulation thickness: 1.2 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
- Ampacity: 223.0 A
3x120mm2
Nexans ref.
- Conductor cross-section: 120 mm²
- Outer Diameter: 43.9 mm
- Approximate weight: 4344.48 kg/km
- Minimum outer sheath thickness: 1.48 mm
- Nominal insulation thickness: 1.2 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
- Ampacity: 223.0 A
4x120mm2
Nexans ref.
- Conductor cross-section: 120 mm²
- Outer Diameter: 49.21 mm
- Approximate weight: 5554.02 kg/km
- Minimum outer sheath thickness: 1.64 mm
- Nominal insulation thickness: 1.2 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
- Ampacity: 223.0 A
2x150mm2
Nexans ref.
- Conductor cross-section: 150 mm²
- Outer Diameter: 45.42 mm
- Approximate weight: 4151.56 kg/km
- Minimum outer sheath thickness: 1.56 mm
- Nominal insulation thickness: 1.4 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
- Ampacity: 251.0 A
3x150mm2
Nexans ref.
- Conductor cross-section: 150 mm²
- Outer Diameter: 49.05 mm
- Approximate weight: 5425.85 kg/km
- Minimum outer sheath thickness: 1.64 mm
- Nominal insulation thickness: 1.4 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
- Ampacity: 251.0 A
4x150mm2
Nexans ref.
- Conductor cross-section: 150 mm²
- Outer Diameter: 54.32 mm
- Approximate weight: 6853.69 kg/km
- Minimum outer sheath thickness: 1.72 mm
- Nominal insulation thickness: 1.4 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
- Ampacity: 251.0 A
2x185mm2
Nexans ref.
- Conductor cross-section: 185 mm²
- Outer Diameter: 50.18 mm
- Approximate weight: 5055.79 kg/km
- Minimum outer sheath thickness: 1.64 mm
- Nominal insulation thickness: 1.6 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
- Ampacity: 281.0 A
3x185mm2
Nexans ref.
- Conductor cross-section: 185 mm²
- Outer Diameter: 53.72 mm
- Approximate weight: 6547.29 kg/km
- Minimum outer sheath thickness: 1.72 mm
- Nominal insulation thickness: 1.6 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
- Ampacity: 281.0 A
4x185mm2
Nexans ref.
- Conductor cross-section: 185 mm²
- Outer Diameter: 59.69 mm
- Approximate weight: 8297.97 kg/km
- Minimum outer sheath thickness: 1.88 mm
- Nominal insulation thickness: 1.6 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
- Ampacity: 281.0 A
2x240mm2
Nexans ref.
- Conductor cross-section: 240 mm²
- Outer Diameter: 61.86 mm
- Approximate weight: 6994.6 kg/km
- Minimum outer sheath thickness: 1.8 mm
- Nominal insulation thickness: 1.7 mm
- Number of cores: 2
- Max. DC resistance of the conductor at 20°C: 0.08 Ohm/km
- Ampacity: 324.0 A
3x240mm2
Nexans ref.
- Conductor cross-section: 240 mm²
- Outer Diameter: 66.68 mm
- Approximate weight: 8983.62 kg/km
- Minimum outer sheath thickness: 1.88 mm
- Nominal insulation thickness: 1.7 mm
- Number of cores: 3
- Max. DC resistance of the conductor at 20°C: 0.08 Ohm/km
- Ampacity: 324.0 A
4x240mm2
Nexans ref.
- Conductor cross-section: 240 mm²
- Outer Diameter: 74.12 mm
- Approximate weight: 11313.05 kg/km
- Minimum outer sheath thickness: 2.04 mm
- Nominal insulation thickness: 1.7 mm
- Number of cores: 4
- Max. DC resistance of the conductor at 20°C: 0.08 Ohm/km
- Ampacity: 324.0 A
Description
Description
Standards
-
ProductIEC 60502-1
Application
Secondary distribution in low voltage. Indoor installations of industrial, commercial and residential buildings that must continue to operate in case of exposure to fire. Suitable for installation in trays, compliance with Tray Cable (TC) flame test. Fire resistance test in accordance with IEC 60331.
Fire Resistance Test (Circuit Integrity): The flame must have sufficient power so that the cable surface reaches a temperature of 750°C 10 minutes after the fire is applied and this must be maintained for 120 minutes.
During this time and up to 15 minutes after the fire is extinguished, the conductors must be energized at Nominal Voltage.
Construction
Soft copper conductor, flexible class 5 wiring, covered with flame retardant mica tape.
Insulation
Cross-linked polyethylene (XLPE) compound.
Jacket
Halogen-free, low-smoke, flame retardant polyolefin compound (HFFR-LS).
Applicable Standards
IEC 60502-1.
Certificate
RETIE N°03475
Operating Voltage
0.6/1(1.2) kV
Identification
Insulation colors according to RETIE:
2 Conductors: Black-White
3 Conductors: Black-White-Green
4 Conductors: Black-White-Red-Green
5 Conductors: Yellow-Blue-Red-White-Green
Black Jacket.
Packaging Unit
500 m or 1000 m reels. Other packaging units available upon request.
Ampacity Conditions
- IEC 60364-5-52, Table B.52.5, Method D1, Duct buried in the ground Ta: 20°C, Tc: 90°C.
- The data indicated in this table are subject to normal manufacturing tolerances.
NOTE:
- Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania