Lisbon - Hawk (320 - 40 mm2)

Description

Description

Application

HVCRC CENTELSA by Nexans cables are designed to improve the current capacity of the line, reduce sag and electrical losses and are used in overhead lines for the transmission of electrical energy. Additionally, they are an excellent alternative for transmission line repowering projects.

Construction

Conductor made of trapezoidal wires of high-conductivity annealed aluminum alloy 1350-O, stranded on a carbon and glass fiber core embedded in a high-temperature thermoset resin.

Reference Standards

  • ASTM B987
  • ASTM B857
  • IEC 62219  

Certificate

RETIE N°06613

Temperature

  • 180°C, Continous operating.
  • 200°C, Emergency by 8760 Hours.

Packaging

Wooden Reels.

Ampacity Conditions

Current Capacity at continous operating temperature of 180°C and 200 °C in emergency, calculated according to IEEE Standard 738-2012 under the following conditions:

  • Wind 2 ft/s (0.61 m/s) with an angle of 90°.
  • Emissivity Coefficient 0.6.
  • Solar Absorption Coefficient 0.5.
  • Ambient temperature 25°C.
  • Solar radiation 93 W/ft2 (1000 W/m2).
  • System Frecuency 50 Hz.

NOTE:

  • The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Type of cable
LISBON / HAWK
Conductor flexibility
Stranded
Conductor material
Aluminum / Composite Core
Conductor shape
Compact Stranded (trapezoidal wires)

Dimensional characteristics

Dimensional characteristics

Aluminium cross-section
316.7 mm²
Cross-section of the cores
39.7 mm²
Conductor cross-section
356.4 mm²
Number of cores
1
Core diameter
7.1 mm
Number of aluminium wires
16
Conductor diameter
21.79 mm
Nominal outer diameter
21.79 mm
Approximate weight
949.5 kg/km

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.09 Ohm/km
Max. Electrical Resistance. AC 50Hz 25°C
0.091 Ohm/km
Max. Electrical Resistance AC 50Hz 75°C
0.109 Ohm/km
Max. Electrical Resistance AC 50Hz 180°C
0.147 Ohm/km
Max. Electrical Resistance AC 50Hz 200°C
0.154 Ohm/km
Inductive reactance
0.222 Ohm/km
Capacitive reactance
0.191 MOhm.km
Ampacity 180°C
1319 A
Ampacity 200°C
1391 A

Mechanical characteristics

Mechanical characteristics

Minimum Tensile Strength Conductor
108.1 kN
Nominal Tensile Strength Core
89.1 kN

Usage characteristics

Usage characteristics

Maximum operating temperature (cables)
180 °C
Packaging
Reel

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.