- Markets
- Catalogue
- Services and solutions
- Company
- Newsroom
- Tools & Resources
- Documents
- Nexans Insights
- Search
- Contact us
- Compare
- Sign in
Medium Voltage Copper 90°C XLPE 15kV 100% PC PVC
Medium Voltage Copper 90°C XLPE 15kV 100% PC PVC
Single Medium Voltage Cables, XLPE Insulated and PVC Jacket.
Read more2 AWG
Nexans ref. 201726
- Conductor cross-section (AWG/KCMIL): 2 AWG
- Total number of wires: 7
- Conductor cross-section: 33.6 mm²
- Conductor diameter: 6.81 mm
- Nominal outer diameter: 21.58 mm
- Approximate weight: 700 kg/km
- Minimum outer sheath thickness: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 0.531 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.68 Ohm/km
- Nominal capacitance: 174.0 pF/m
- Perm current rating in air 40°C: 195 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 155 A
- Phase reactance 60 Hz - flat formation: 0.181 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.163 Ohm/km
- Maximum Pull Tension of Conductor: 2 kN
- Minimum repeated bending diameter: 259 mm
1/0 AWG
Nexans ref. 201745
- Conductor cross-section (AWG/KCMIL): 1/0 AWG
- Total number of wires: 19
- Conductor cross-section: 53.5 mm²
- Conductor diameter: 8.52 mm
- Nominal outer diameter: 24.05 mm
- Approximate weight: 963 kg/km
- Minimum outer sheath thickness: 1.78 mm
- Max. DC resistance of the conductor at 20°C: 0.335 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.428 Ohm/km
- Nominal capacitance: 200.0 pF/m
- Perm current rating in air 40°C: 260 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 200 A
- Phase reactance 60 Hz - flat formation: 0.169 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.151 Ohm/km
- Maximum Pull Tension of Conductor: 4 kN
- Minimum repeated bending diameter: 289 mm
2/0 AWG
Nexans ref. 201757
- Conductor cross-section (AWG/KCMIL): 2/0 AWG
- Total number of wires: 19
- Conductor cross-section: 67.4 mm²
- Conductor diameter: 9.57 mm
- Nominal outer diameter: 25.1 mm
- Approximate weight: 1121 kg/km
- Minimum outer sheath thickness: 1.78 mm
- Max. DC resistance of the conductor at 20°C: 0.266 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.34 Ohm/km
- Nominal capacitance: 216.0 pF/m
- Perm current rating in air 40°C: 300 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 230 A
- Phase reactance 60 Hz - flat formation: 0.163 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.146 Ohm/km
- Maximum Pull Tension of Conductor: 5 kN
- Minimum repeated bending diameter: 301 mm
3/0 AWG
Nexans ref.
- Conductor cross-section (AWG/KCMIL): 3/0 AWG
- Total number of wires: 19
- Conductor cross-section: 85 mm²
- Conductor diameter: 10.75 mm
- Nominal outer diameter: 26.28 mm
- Approximate weight: 1313 kg/km
- Minimum outer sheath thickness: 1.78 mm
- Max. DC resistance of the conductor at 20°C: 0.21 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.269 Ohm/km
- Nominal capacitance: 234.0 pF/m
- Perm current rating in air 40°C: 345 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 260 A
- Phase reactance 60 Hz - flat formation: 0.158 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.141 Ohm/km
- Maximum Pull Tension of Conductor: 6 kN
- Minimum repeated bending diameter: 315 mm
4/0 AWG
Nexans ref.
- Conductor cross-section (AWG/KCMIL): 4/0 AWG
- Total number of wires: 19
- Conductor cross-section: 107 mm²
- Conductor diameter: 12.1 mm
- Nominal outer diameter: 27.6 mm
- Approximate weight: 1551 kg/km
- Minimum outer sheath thickness: 1.78 mm
- Max. DC resistance of the conductor at 20°C: 0.167 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.214 Ohm/km
- Nominal capacitance: 254.0 pF/m
- Perm current rating in air 40°C: 400 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 295 A
- Phase reactance 60 Hz - flat formation: 0.153 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.136 Ohm/km
- Maximum Pull Tension of Conductor: 7 kN
- Minimum repeated bending diameter: 331 mm
250 kcmil
Nexans ref.
- Conductor cross-section (AWG/KCMIL): 250 KCMIL
- Total number of wires: 37
- Conductor cross-section: 127 mm²
- Conductor diameter: 13.25 mm
- Nominal outer diameter: 28.78 mm
- Approximate weight: 1755 kg/km
- Minimum outer sheath thickness: 1.78 mm
- Max. DC resistance of the conductor at 20°C: 0.142 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.181 Ohm/km
- Nominal capacitance: 271.0 pF/m
- Perm current rating in air 40°C: 445 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 325 A
- Phase reactance 60 Hz - flat formation: 0.145 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.127 Ohm/km
- Maximum Pull Tension of Conductor: 9 kN
- Minimum repeated bending diameter: 345 mm
350 kcmil
Nexans ref.
- Conductor cross-section (AWG/KCMIL): 350 KCMIL
- Total number of wires: 37
- Conductor cross-section: 177 mm²
- Conductor diameter: 15.68 mm
- Nominal outer diameter: 31.21 mm
- Approximate weight: 2285 kg/km
- Minimum outer sheath thickness: 1.78 mm
- Max. DC resistance of the conductor at 20°C: 0.101 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.13 Ohm/km
- Nominal capacitance: 308.0 pF/m
- Perm current rating in air 40°C: 550 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 390 A
- Phase reactance 60 Hz - flat formation: 0.141 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.124 Ohm/km
- Maximum Pull Tension of Conductor: 12 kN
- Minimum repeated bending diameter: 375 mm
500 kcmil
Nexans ref.
- Conductor cross-section (AWG/KCMIL): 500 KCMIL
- Total number of wires: 37
- Conductor cross-section: 253 mm²
- Conductor diameter: 18.74 mm
- Nominal outer diameter: 34.27 mm
- Approximate weight: 3048 kg/km
- Minimum outer sheath thickness: 1.78 mm
- Max. DC resistance of the conductor at 20°C: 0.071 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.092 Ohm/km
- Nominal capacitance: 353.0 pF/m
- Perm current rating in air 40°C: 685 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 465 A
- Phase reactance 60 Hz - flat formation: 0.135 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.118 Ohm/km
- Maximum Pull Tension of Conductor: 17 kN
- Minimum repeated bending diameter: 411 mm
Description
Description
Standards
-
ProductASTM B 496; ASTM B 8; ICEA S-93-639; UL 1072
Application
Medium Voltage single core cables are used in energy distribution networks, as feeders for transformers in substations, industrial facilities and urbanizations. They are suitable for installations in dry or wet locations, outdoors and in underground ducts.
Construction
1. Conductor: Plain annealed Copper, compact class B stranding.
2. Conductor screen: Extruded semiconductive compound.
3. Insulation: Cross-linked Polyethylene (XLPE).
4. Insulation screen: Strippable semiconductive compund.
These last three components extruded in CV (continuous vulcanization) of tripleextrusion in the dry curing process.
5. Screen: : Made up of copper tape.
6. Outer jacket: PVC compound, flame retardant, resistant to heat, abrasion and humidity, resistant to sunlight (SR), black color.
Applicable Standards
ICEA S-93-639, NTC 2186-2, NEMA WC 74.
Certificate
RETIE N° 00412
Operating Temperature
90 °C.
Operating Voltage
15 kV.
Identification
Insulation in natural color and black external jacket. Sequential length meter by meter with return to zero.
Unit Packaging
500 m or 1000 m reels. Other packaging units available upon request.
Optional Features available upon request:
Insulation in XLPE-TR (Tree retardant) compound. External covering in HDPE, LDPE or XLPE. Application of additives for protection against rodents and termites. Water blocking system in conductor and/or screen, longitudinal and/or radial.
For more information, contact our sales representative
Ampacity and Reactance Conditions
- Ampacities of Insulated Single Copper Conductor Isolated in Air Based on Conductor Temperatures of 90°C and Ambient Air Temperature of 40°C. According to NEC, Table 310.60(C)(69).
- Ampacities of Three Single-Insulated Copper Conductors in Underground Electrical Ducts (Three Conductors per Electrical Duct) Based on Ambient Earth Temperature of 20°C, 100% Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C. According to NEC, Table 310.60(C)(77).
- Reactance Inductive to 90°C, 60Hz, 3 conductors spaced 1 diameter. Trifoil and flat configuration.
NOTE:
- The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
- Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantitie.
RECOMMENDATIONS FOR THE SELECTION OF ACCESSORIES AND DUCTS
The technical information presented here is for reference purposes only. Actual dimensions and construction details will only be available with the test reports for each manufacturing order. For the selection of accessories and/or ducts, it is recommended to measure directly on the actual dimensions of the cable using the appropriate methods and instruments. Centelsa by Nexans will not assume any responsibility for the selection of such elements.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania