266.8 KCMIL
Description
Description
Standards
-
NationalNTC 308; NTC 360
Application
AAC CENTELSA by Nexans cables are used in overhead power transmission and distribution networks.
Construction
Concentric conductor composed of aluminum wires 1350-H19.
Applicable Standards
- ASTM B230, NTC 360
- ASTM B231, NTC 308
Certificate
RETIE N°07983
RETIE N° 00409
Ampacity Conditions
- Current capacity at ambient temperature 25°C, conductor temperature 75°C, solar emission 1kW/m², absorption and emissivity coefficients 0.5, wind speed 610 mm/sec, at sea level and at 60 Hz.
- Short circuit current for one (1.0) second, at initial temperature of 75°C and final temperature of 340°C.
- For all constructions or wiring ME: Modulus of elasticity 6300 kgf/mm², CDL: linear expansion coefficient 23.0 x 10 exp(-6) /°C.
NOTE:
- The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
- Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantitie
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class AA
Conductor material
Aluminum Alloy 1350-H19
Conductor shape
Circular stranded (RM)
Type of cable
Daisy
Type of conductor
Stranded
Dimensional characteristics
Dimensional characteristics
Outer Diameter
14.88 mm
Number of aluminium wires
7
Diameter of aluminium wires
4.96 mm
Conductor cross-section
134.6 kcmil
Aluminium cross-section
134.6 mm²
Approximate weight
373 kg/km
Conductor cross-section (AWG/KCMIL)
266.8 KCMIL
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
0.217 Ohm/km
Ampacity
443.0 A
Short Circuit Current 1 s Max
15.6 kA
Mechanical characteristics
Mechanical characteristics
Minimum breaking load
2190 kgf
Hardness type
1350-H19
Usage characteristics
Usage characteristics
Maximum operating temperature
75 °C