1x4+4

Description

Description

Standards

  • Product
    ASTM B 232; ICEA S-76-474
  • National
    NTC 309; NTC 5346

Applications

Multiplex cables are used in aerial secondary distribution systems, in public lighting or in temporary construction installations, connection with the transformer to the point of derivation for the user or connection with the distribution box.

Construction

Phase Conductor

Aluminum 1350-H19 hard tempering, concentric stranded.

Neutral Conductor

Aluminum support conductor with Steel Core (ACSR), concentric stranded.

Insulation

Composed of cross-linked polyethylene XLPE, resistant to UV rays.

Applicable standards

  • NTC 5346, ICEA S-76-474.
  • NTC 4334, ASTM B-400.
  • NTC 309, ASTM B-232.

Certificate

RETIE and NTC N° 02619/01336

Operating Temperature

90°C

Operating Voltage

600V.

Identification

• Phase conductors identification by polarity ridges.

Opcional

• Neutral conductor insulated.

• flame retardant.

• Other configuration and marking are available upon request

Testing Conditions

  • Data indicated in this table are subject to normal manufacturing tolerances.
  • Admissible current according to NTC 2050 Table 310.15(B)(20). Cables secured by messenger for ambient temperature of 40°C and conductor temperature of 90°C.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Phase Conductor Type
AAC - All Aluminium Conductor
Neutral Type
ACSR - Aluminium Conductor Steel Reinforced
Insulation
XLPE
Conductor flexibility
Class B
Conductor material
Aluminum Alloy 1350
Conductor shape
Compact stranded

Dimensional characteristics

Dimensional characteristics

Approximate weight
173 kg/km
Conductor cross-section
21.14 mm²
Conductor diameter
5.53 mm
Neutral Conductor Diameter
6.35 mm
Nominal insulation thickness
1.14 mm
Nominal outer diameter
14.26 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Ampacity
91.0 A
Max. DC resistance of the conductor at 20°C
1.414 Ohm/km
Operating voltage
600 V

Mechanical characteristics

Mechanical characteristics

Rated breaking load
844 kgf

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Packaging
Reel
Short-circuit max. conductor temperature
250 °C
U.V resistance
Yes

Resources

Resources

Selling & delivery Information

Packaging
Reels by multiple wooden, length 500 o 1000 m.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close