TECK 90 600 V 3x2/0+1x6 AWG

Description

Description

Standards

  • Product
    CSA C22.2 N° 131; CSA C22.2 N° 2556; CSA C22.2 N° 38
  • Test
    CSA C22.2 N° 03-01; UL 2556

Application:

General application in low voltage distribution networks in operating stations where high mechanical strength is required. The interlocked aluminum armour gives greater flexibility compared to the traditional steel armour and the type of conformation of the same make has a high resistance to loads that could be placed on it. Class I, Div.2 and Class II, Div.2 hazardous locations per NEC.

Construction:

1. Conductor: Soft copper, class B.

2. Insulation: Cross linked polyethylene XLPE.

3. Bare grounding conductor: Soft copper, class B.

4. Inner covering: Anti-flame compound polyvinyl chloride PVC.

5. Armour: Interlocked aluminum tape.

6. Outer sheath: Anti-flame compound polyvinyl chloride PVC.

Main characteristics:

Resistance to abrasion and oils. Resistance to weather and sunlight. Its armour provides additional mechanical protection and provides greater flexibility compared with other types of armour. Does not propagate the FT-1 flame. Fire retardant according to C22.2 No 0.3-01/FT-4. Resistance to attack by rodents.

Gauge:

From 14 AWG up to 500 kcmil.

Marking:

For gauges equal to or smaller than 8 AWG: INDECO S.A. TECK90(XLPE) (Nb. cores x Gauge phase cond. + Gauge ground. cond.) 0,6 kV -25C FT1 FT4 SR CSA 255079 - Year - Sequential length.

For gauges higher than 8 AWG: INDECO S.A. TECK90(XLPE) (Nb. cores x Gauge phase cond. + Gauge ground. cond.) 0,6 kV -40C FT1 FT4 SR CSA 255079 - year - Sequential length.

Packing:

Non returnable wooden reels.

Colour:

Insulation: See core identification.

Outer sheath: Black.

International standards

CSA C22.2 Nº 131-14: Type TECK 90 cable.

CSA C22.2 Nº 38-14: Thermoset-insulated wires and cables.

CSA C22.2 Nº 03-01: Test methods for electrical wires and cables.

CSA C22.2 Nº 2556-15: Wire and cable test methods.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.

BENDING RADIUS WHEN INSTALLED

R = f x D
R: Bending radius when installed (mm).
f: Multiplicative factor.
D: Cable nominal outer diameter (mm).

Calculation of Current Condition TECK 90

BASED ON CEC, PART 1, TABLE 2

Maximum conductor temperature: 90°C.

Ambient temperature: 30°C.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulating material
XLPE
Inner sheath
Flame retardant PVC
Armour type
Interlocked aluminum tape
Outer sheath
Flame retardant PVC
Sheath colour
Black
Number of conductors
3
Conductor flexibility
Class B ASTM B8
Conductor shape
Compact stranded

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section (AWG/KCMIL)
2/0 AWG
Conductor diameter
9.7 mm
Minimum insulation thickness
1.4 mm
Ground Conductor cross-section (AWG)
6
Diameter over inner sheath
31.5 mm
Diameter over armour
37.1 mm
Diameter over Sheath
39.2 mm
Approximate weight
3161 kg/km
Inner sheath thickness
2.03 mm
Minimum outer sheath thickness
1.0 mm

Electrical characteristics

Electrical characteristics

Dielectric strength
7.0 kV
Max. DC resistance of the conductor at 20°C
0.2713 Ohm/km
Nominal capacitance
531.0 pF/m
Operating voltage
0.6 kV
Perm current rating in air 30°C
185 A
Time of application Dielectric strength core to screen DC
1 min.

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Excellent

Usage characteristics

Usage characteristics

Flame retardant
-
Fire retardant
FT4 (C22.2 No. 0.3-01/4.11.4)
Oil resistance
Good
Rodent protection
Corrugated aluminium tape
Bending factor when installed
- (xD)
U.V resistance
-
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C
Reference
09

Resources

Resources

Documentation

xlsx — 0 B

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close