70 mm2

Description

Description

Standards

  • Product
    IEC 60502-1

APPLICATION

Secondary distribution in low voltage. Indoor installations of industrial, commercial and residential buildings that must continue to operate in case of exposure to fire. Suitable for installation in trays, compliance with Tray Cable (TC) flame test. Fire resistance test in accordance with IEC 60331.

Fire Resistance Test (Circuit Integrity): The flame must have sufficient power so that the cable surface reaches a temperature of 750°C 10 minutes after the fire is applied and this must be maintained for 120 minutes.

During this time and up to 15 minutes after the fire is extinguished, the conductors must be energized at Nominal Voltage.

Construction

Conductor

Soft copper conductor, flexible class 5 wiring, covered with flame retardant mica tape. 

Insulation

Cross-linked polyethylene (XLPE) compound.

Jacket

Halogen-free, low-smoke, flame retardant polyolefin compound (HFFR-LS).

Applicable Standard

IEC 60502-1.

Certificate

RETIE N°03475

Operating Voltage

0.6/1(1.2) kV

Identification

Insulation in natural base color.

Black Jacket.

Packaging Unit

500 m or 1000 m reels. Other packaging units available upon request.

Ampacity Conditions

  • IEC 60364-5-52, Table B.52.5, Method D1, Duct buried in the ground Ta: 20°C, Tc: 90°C.
  • NBR 5410, Table 39, Method F, single cables laid flat (Horizontal or Vertical) in air, Ta: 30°C, Tc: 90°C, sizes 1.5 to 16 mm2.
  • IEC 60364-5-52, Table B.52.12, Method F, single cables laid flat (Horizontal or Vertical) in air, Ta: 30°C, Tc: 90°C.
  • The data indicated in this table are subject to normal manufacturing tolerances.

NOTE:

  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Conductor flexibility
Class 5
Conductor shape
Bunched Wires
Insulation
XLPE
Halogen free
Yes
Outer sheath
HFFR (Halogen Free Flame Retardant)

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
70 mm²
Outer Diameter
15.68 mm
Approximate weight
705.87 kg/km
Nominal insulation thickness
1.1 mm
Nominal outer diameter
15.68 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.272 Ohm/km
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Permissible current rating buried/duct 20°C
167 A
Perm. current rating in air 30°C - flat formation
279 A

Mechanical characteristics

Mechanical characteristics

Abrasion resistance
Good

Usage characteristics

Usage characteristics

Fire resistant
IEC 60331
Flame retardant
IEC 60332-3-24
Smoke density
IEC 61034-2
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close