Medium Voltage Copper 90°C XLPE 35kV 100% PC PVC

Products

1/0 AWG

Nexans ref.

  • Conductor cross-section (AWG/KCMIL): 1/0 AWG
  • Total number of wires: 19
  • Conductor cross-section: 53.5 mm²
  • Conductor diameter: 8.52 mm
  • Nominal outer diameter: 32.55 mm
  • Approximate weight: 1360.22 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.335 Ohm/km
  • Max. Electrical Resistance AC 60Hz 90°C: 0.428 Ohm/km
  • Nominal capacitance: 126.0 pF/m
  • Perm current rating in air 40°C: 260 A
  • Permissible current rating buried/duct 20°C - Trefoil formation: 200 A
  • Phase reactance 60 Hz - flat formation: 0.192 Ohm/km
  • Phase reactance 60 Hz - trefoil formation: 0.174 Ohm/km
  • Maximum Pull Tension of Conductor: 4 kN
  • Minimum repeated bending diameter: 391 mm

 

2/0 AWG

Nexans ref. 201762

  • Conductor cross-section (AWG/KCMIL): 2/0 AWG
  • Total number of wires: 19
  • Conductor cross-section: 67.4 mm²
  • Conductor diameter: 9.57 mm
  • Nominal outer diameter: 33.6 mm
  • Approximate weight: 1531.12 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.266 Ohm/km
  • Max. Electrical Resistance AC 60Hz 90°C: 0.34 Ohm/km
  • Nominal capacitance: 134.0 pF/m
  • Perm current rating in air 40°C: 300 A
  • Permissible current rating buried/duct 20°C - Trefoil formation: 230 A
  • Phase reactance 60 Hz - flat formation: 0.185 Ohm/km
  • Phase reactance 60 Hz - trefoil formation: 0.168 Ohm/km
  • Maximum Pull Tension of Conductor: 5 kN
  • Minimum repeated bending diameter: 404 mm

 

3/0 AWG

Nexans ref.

  • Conductor cross-section (AWG/KCMIL): 3/0 AWG
  • Total number of wires: 19
  • Conductor cross-section: 85 mm²
  • Conductor diameter: 10.75 mm
  • Nominal outer diameter: 34.78 mm
  • Approximate weight: 1737.79 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.21 Ohm/km
  • Max. Electrical Resistance AC 60Hz 90°C: 0.269 Ohm/km
  • Nominal capacitance: 143.0 pF/m
  • Perm current rating in air 40°C: 345 A
  • Permissible current rating buried/duct 20°C - Trefoil formation: 260 A
  • Phase reactance 60 Hz - flat formation: 0.179 Ohm/km
  • Phase reactance 60 Hz - trefoil formation: 0.162 Ohm/km
  • Maximum Pull Tension of Conductor: 6 kN
  • Minimum repeated bending diameter: 418 mm

 

4/0 AWG

Nexans ref. 201787

  • Conductor cross-section (AWG/KCMIL): 4/0 AWG
  • Total number of wires: 19
  • Conductor cross-section: 107 mm²
  • Conductor diameter: 12.07 mm
  • Nominal outer diameter: 36.1 mm
  • Approximate weight: 1991.77 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.167 Ohm/km
  • Max. Electrical Resistance AC 60Hz 90°C: 0.214 Ohm/km
  • Nominal capacitance: 154.0 pF/m
  • Perm current rating in air 40°C: 395 A
  • Permissible current rating buried/duct 20°C - Trefoil formation: 295 A
  • Phase reactance 60 Hz - flat formation: 0.173 Ohm/km
  • Phase reactance 60 Hz - trefoil formation: 0.156 Ohm/km
  • Maximum Pull Tension of Conductor: 7 kN
  • Minimum repeated bending diameter: 434 mm

 

250 kcmil

Nexans ref.

  • Conductor cross-section (AWG/KCMIL): 250 KCMIL
  • Total number of wires: 37
  • Conductor cross-section: 127 mm²
  • Conductor diameter: 13.25 mm
  • Nominal outer diameter: 37.28 mm
  • Approximate weight: 2209.92 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.142 Ohm/km
  • Max. Electrical Resistance AC 60Hz 90°C: 0.181 Ohm/km
  • Nominal capacitance: 163.0 pF/m
  • Perm current rating in air 40°C: 440 A
  • Permissible current rating buried/duct 20°C - Trefoil formation: 325 A
  • Phase reactance 60 Hz - flat formation: 0.168 Ohm/km
  • Phase reactance 60 Hz - trefoil formation: 0.15 Ohm/km
  • Maximum Pull Tension of Conductor: 9 kN
  • Minimum repeated bending diameter: 448 mm

 

350 kcmil

Nexans ref.

  • Conductor cross-section (AWG/KCMIL): 350 KCMIL
  • Total number of wires: 37
  • Conductor cross-section: 177 mm²
  • Conductor diameter: 15.68 mm
  • Nominal outer diameter: 39.71 mm
  • Approximate weight: 2770.31 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.101 Ohm/km
  • Max. Electrical Resistance AC 60Hz 90°C: 0.13 Ohm/km
  • Nominal capacitance: 182.0 pF/m
  • Perm current rating in air 40°C: 545 A
  • Permissible current rating buried/duct 20°C - Trefoil formation: 390 A
  • Phase reactance 60 Hz - flat formation: 0.16 Ohm/km
  • Phase reactance 60 Hz - trefoil formation: 0.142 Ohm/km
  • Maximum Pull Tension of Conductor: 12 kN
  • Minimum repeated bending diameter: 477 mm

 

500 kcmil

Nexans ref.

  • Conductor cross-section (AWG/KCMIL): 500 KCMIL
  • Total number of wires: 37
  • Conductor cross-section: 253 mm²
  • Conductor diameter: 18.74 mm
  • Nominal outer diameter: 42.77 mm
  • Approximate weight: 3571.11 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.071 Ohm/km
  • Max. Electrical Resistance AC 60Hz 90°C: 0.092 Ohm/km
  • Nominal capacitance: 206.0 pF/m
  • Perm current rating in air 40°C: 680 A
  • Permissible current rating buried/duct 20°C - Trefoil formation: 465 A
  • Phase reactance 60 Hz - flat formation: 0.152 Ohm/km
  • Phase reactance 60 Hz - trefoil formation: 0.134 Ohm/km
  • Maximum Pull Tension of Conductor: 17 kN
  • Minimum repeated bending diameter: 514 mm

 

Description

Description

Standards

  • Product
    ASTM B 496; ASTM B 8; ICEA S-93-639; UL 1072

Application

Medium Voltage single core cables are used in electrical energy distribution networks, as feeders for transformers in substations, industrial facilities and urbanizations. They are suitable for installations in dry or wet locations, outdoors and in underground ducts.

Construction

​1. Conductor: Plain annealed Copper, compact class B stranding.

2. Conductor screen: Extruded semiconductive compound.

3. Insulation: Cross-linked Polyethylene (XLPE).

4. Insulation screen: Strippable semiconductive compund.

These last three components extruded in CV (continuous vulcanization) of triple extrusion in the dry curing process.

5. Screen: : Made up of copper tape.

6. Outer jacket: PVC compound, flame retardant, resistant to heat, abrasion and humidity, resistant to sunlight (SR), black color. 

Applicable Standards

ICEA S-93-639, NTC 2186-2, NEMA WC 74.

Certificate

RETIE  N° 00412

Operating Temperature

90 °C.

Operating Voltage

35 kV.

Identification

Insulation in natural color and black external jacket. Sequential length meter by meter with return to zero.

Unit Packaging

500 m or 1000 m reels. Other packaging units available upon request.

Optional Features available upon request:

Insulation in XLPE-TR (Tree retardant) compound. External covering in HDPE, LDPE or XLPE. Application of additives for protection against rodents and termites. Water blocking system in conductor and/or screen, longitudinal and/or radial.

For more information, contact our sales representative.

Ampacity and Reactance Conditions

  • Ampacities of Insulated Single Copper Conductor Isolated in Air Based on Conductor Temperatures of 90°C and Ambient Air Temperature of 40°C. According to NEC, Table 310.60(C)(69).
  • Ampacities of Three Single-Insulated Copper Conductors in Underground Electrical Ducts (Three Conductors per Electrical Duct) Based on Ambient Earth Temperature of 20°C, 100% Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C. According to NEC, Table 310.60(C)(77).
  • Reactance Inductive to 90°C, 60Hz, 3 conductors spaced 1 diameter. Trifoil and flat configuration.

NOTE:

  • The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantitie.

RECOMMENDATIONS FOR THE SELECTION OF ACCESSORIES AND DUCTS

The technical information presented here is for reference purposes only. Actual dimensions and construction details will only be available with the test reports for each manufacturing order. For the selection of accessories and/or ducts, it is recommended to measure directly on the actual dimensions of the cable using the appropriate methods and instruments. Centelsa by Nexans will not assume any responsibility for the selection of such elements.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Conductor shape
Circular compacted
Conductor flexibility
Class B
Insulation
XLPE (Cross-linked Polyethylene)
Screen
Copper tape
Jacket material
PVC

Dimensional characteristics

Dimensional characteristics

Minimum insulation thickness
8.38 mm
Minimum outer sheath thickness
1.78 mm

Electrical characteristics

Electrical characteristics

Insulation Level
100 %
Maximum rated voltage
35 kV
Dielectric strength core to screen AC
69.0 kV
Time of application Dielectric strength core to screen AC
5 min.
Maximal partial discharge test
5 pC

Usage characteristics

Usage characteristics

Flame retardant
IEC 60332-1-2
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C
U.V resistance
UL 2556 - Sunlight Resistance
Oil resistance
ICEA S-93-639 (70°C/4h)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close