500 kcmil

Description

Description

Standards

  • Product
    ASTM B 230; ICEA S-94-649

Application

Medium Voltage single core cables are used in electrical energy distribution networks, as feeders for transformers in substations, industrial facilities and urbanizations. They are suitable for installations in dry or wet locations, outdoors, underground ducts or directly buried in earth.

Construction

​1. Conductor: Aluminum, compacted class B stranding..

2. Conductor screen: Extruded semiconductive compound.

3. Insulation: Cross-linked Polyethylene (XLPE). 

4. Insulation screen: Strippable semiconductive compund.

These last three components extruded in CV (continuous vulcanization) of triple extrusion in the dry curing process.

5. Concentric Neutral: Made up of round copper wires with a total cross section equal to one third of phase conductor section (N=1/3), with a non-hygroscopic separator tape over the wires.

6. Outer jacket: PVC compound, flame retardant, resistant to heat, abrasion and humidity, resistant to sunlight (SR), black color.

Applicable Standards

ICEA S-94-649, NTC 2186-1.

Certificate

RETIE  N° 05196

Operating Temperature

90 °C

Operating Voltage

35 kV

Identification

Insulation in natural color and black external jacket. Sequential length meter by meter with return to zero.

Unit Packaging

500 m or 1000 m reels. Other packaging units available upon request.

Optional Features available upon request:

Insulation in XLPE-TR (Tree retardant) compound. External covering in HDPE, LDPE or XLPE. Application of additives for protection against rodents and termites. Water blocking system in conductor and/or screen, longitudinal and/or radial.

For more information, contact our sales representative.

Ampacity and Reactance Conditions

  • Ampacities of Insulated Single Aluminum Conductor Isolated in Air Based on Conductor Temperatures of 90° C and Ambient Air Temperature of 40°C. According to NEC, Table 310.60(C)(70).
  • Ampacities of Three Single-Insulated Aluminum Conductors in Underground Electrical Ducts (Three Conductors per Electrical Duct) Based on Ambient Earth Temperature of 20°C, 100% Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C. According to NEC, Table 310.60(C)(78).
  • Reactance Inductive to 90°C, 60Hz, 3 conductors spaced 1 diameter. Trifoil and flat configuration

NOTE:

  • The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantitie.

RECOMMENDATIONS FOR THE SELECTION OF ACCESSORIES AND DUCTS

The technical information presented here is for reference purposes only. Actual dimensions and construction details will only be available with the test reports for each manufacturing order. For the selection of accessories and/or ducts, it is recommended to measure directly on the actual dimensions of the cable using the appropriate methods and instruments. Centelsa by Nexans will not assume any responsibility for the selection of such elements.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum Alloy 1350
Conductor shape
Circular compacted
Conductor flexibility
Class B
Insulation
Cross-linked polyethylene
Neutral Type
Concentric Copper Wires, N=1/3
Jacket material
PVC

Dimensional characteristics

Dimensional characteristics

Conductor cross-section (AWG/KCMIL)
500 KCMIL
Total number of wires
37
Conductor cross-section
253 mm²
Conductor diameter
18.74 mm
Minimum insulation thickness
8.38 mm
Nominal outer diameter
48.31 mm
Approximate weight
2652.93 kg/km
Minimum outer sheath thickness
2.54 mm

Electrical characteristics

Electrical characteristics

Insulation Level
100 %
Maximum rated voltage
35 kV
Dielectric strength core to screen AC
69.0 kV
Time of application Dielectric strength core to screen AC
5 min.
Maximal partial discharge test
5 pC
Max. DC resistance of the conductor at 20°C
0.116 Ohm/km
Max. Electrical Resistance AC 60Hz 90°C
0.149 Ohm/km
Nominal capacitance
206.0 pF/m
Perm current rating in air 40°C
530 A
Permissible current rating buried/duct 20°C - Trefoil formation
370 A
Phase reactance 60 Hz - flat formation
0.161 Ohm/km
Phase reactance 60 Hz - trefoil formation
0.144 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum Pull Tension of Conductor
13 kN
Minimum repeated bending diameter
580 mm
Abrasion resistance
Excellent

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C
U.V resistance
ICEA S-94-649, (720 hours)
Oil resistance
ICEA S-94-649 (70°C/4h)
RoHS compliant
Yes
Flame retardant
IEC 60332-1-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close