VFD CABLES Cu 90°C 600 V PC XLPE/PVC TC
VFD CABLES Cu 90°C 600 V PC XLPE/PVC TC
Multi-conductor VFD cables made with XLPE-insulated Flexible copper conductors, general shielding and PVC outer jacket.
Read more3x500+3x6AWG
Nexans ref. 208995
- Conductor cross-section: 253 mm²
- Conductor cross-section (AWG/KCMIL): 500
- Conductor diameter: 21.8 mm
- Nominal insulation thickness: 1.65 mm
- Ground Conductor cross-section (AWG): 6
- Minimum Insulation thickness of ground cable: 1.02 mm
- Nominal outer diameter: 61.8 mm
- Approximate weight: 9502.75 kg/km
- Max. DC resistance of the conductor at 20°C: 0.074 Ohm/km
- Ampacity: 430.0 A
- Minimum repeated bending diameter: 742 mm
3x350+3x6AWG
Nexans ref. 208234
- Conductor cross-section: 177 mm²
- Conductor cross-section (AWG/KCMIL): 350
- Conductor diameter: 18.01 mm
- Nominal insulation thickness: 1.65 mm
- Ground Conductor cross-section (AWG): 6
- Minimum Insulation thickness of ground cable: 1.02 mm
- Nominal outer diameter: 53.63 mm
- Approximate weight: 7007.16 kg/km
- Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
- Ampacity: 350.0 A
- Minimum repeated bending diameter: 644 mm
3x300+3x6AWG
Nexans ref. 208847
- Conductor cross-section: 152 mm²
- Conductor cross-section (AWG/KCMIL): 300
- Conductor diameter: 16.55 mm
- Nominal insulation thickness: 1.65 mm
- Ground Conductor cross-section (AWG): 6
- Minimum Insulation thickness of ground cable: 1.02 mm
- Nominal outer diameter: 50.49 mm
- Approximate weight: 6207.31 kg/km
- Max. DC resistance of the conductor at 20°C: 0.122 Ohm/km
- Ampacity: 320.0 A
- Minimum repeated bending diameter: 606 mm
3x250+3x6AWG
Nexans ref. 204230
- Conductor cross-section: 127 mm²
- Conductor cross-section (AWG/KCMIL): 250
- Conductor diameter: 15.1 mm
- Nominal insulation thickness: 1.65 mm
- Ground Conductor cross-section (AWG): 6
- Minimum Insulation thickness of ground cable: 1.02 mm
- Nominal outer diameter: 47.36 mm
- Approximate weight: 5317.12 kg/km
- Max. DC resistance of the conductor at 20°C: 0.147 Ohm/km
- Ampacity: 290.0 A
- Minimum repeated bending diameter: 568 mm
3x4/0+3x8AWG
Nexans ref. 209044
- Conductor cross-section: 107 mm²
- Conductor cross-section (AWG/KCMIL): 4/0
- Conductor diameter: 13.54 mm
- Nominal insulation thickness: 1.4 mm
- Ground Conductor cross-section (AWG): 8
- Minimum Insulation thickness of ground cable: 1.02 mm
- Nominal outer diameter: 41.62 mm
- Approximate weight: 4254.08 kg/km
- Max. DC resistance of the conductor at 20°C: 0.174 Ohm/km
- Ampacity: 260.0 A
- Minimum repeated bending diameter: 499 mm
3x2/0+3x10AWG
Nexans ref. 207797
- Conductor cross-section: 67.4 mm²
- Conductor cross-section (AWG/KCMIL): 2/0
- Conductor diameter: 10.74 mm
- Nominal insulation thickness: 1.4 mm
- Ground Conductor cross-section (AWG): 10
- Minimum Insulation thickness of ground cable: 0.68 mm
- Nominal outer diameter: 35.69 mm
- Approximate weight: 2895.76 kg/km
- Max. DC resistance of the conductor at 20°C: 0.276 Ohm/km
- Ampacity: 195.0 A
- Minimum repeated bending diameter: 428 mm
3x1/0+3x10AWG
Nexans ref. 207796
- Conductor cross-section: 53.5 mm²
- Conductor cross-section (AWG/KCMIL): 1/0
- Conductor diameter: 9.54 mm
- Nominal insulation thickness: 1.4 mm
- Ground Conductor cross-section (AWG): 10
- Minimum Insulation thickness of ground cable: 0.68 mm
- Nominal outer diameter: 33.0 mm
- Approximate weight: 2411.73 kg/km
- Max. DC resistance of the conductor at 20°C: 0.345 Ohm/km
- Ampacity: 170.0 A
- Minimum repeated bending diameter: 396 mm
3x2+3x10AWG
Nexans ref. 208235
- Conductor cross-section: 33.6 mm²
- Conductor cross-section (AWG/KCMIL): 2
- Conductor diameter: 7.56 mm
- Nominal insulation thickness: 1.14 mm
- Ground Conductor cross-section (AWG): 10
- Minimum Insulation thickness of ground cable: 0.68 mm
- Nominal outer diameter: 27.57 mm
- Approximate weight: 1662.61 kg/km
- Max. DC resistance of the conductor at 20°C: 0.549 Ohm/km
- Ampacity: 130.0 A
- Minimum repeated bending diameter: 331 mm
3x4+3x12AWG
Nexans ref. 209068
- Conductor cross-section: 21.2 mm²
- Conductor cross-section (AWG/KCMIL): 4
- Conductor diameter: 5.95 mm
- Nominal insulation thickness: 1.14 mm
- Ground Conductor cross-section (AWG): 12
- Minimum Insulation thickness of ground cable: 0.68 mm
- Nominal outer diameter: 24.12 mm
- Approximate weight: 1169.81 kg/km
- Max. DC resistance of the conductor at 20°C: 0.865 Ohm/km
- Ampacity: 95.0 A
- Minimum repeated bending diameter: 289 mm
3x6+3x12AWG
Nexans ref. 209067
- Conductor cross-section: 13.3 mm²
- Conductor cross-section (AWG/KCMIL): 6
- Conductor diameter: 4.776 mm
- Nominal insulation thickness: 1.14 mm
- Ground Conductor cross-section (AWG): 12
- Minimum Insulation thickness of ground cable: 0.68 mm
- Nominal outer diameter: 22.91 mm
- Approximate weight: 945.64 kg/km
- Max. DC resistance of the conductor at 20°C: 1.38 Ohm/km
- Ampacity: 75.0 A
- Minimum repeated bending diameter: 275 mm
3x8+3x14AWG
Nexans ref. 208720
- Conductor cross-section: 8.37 mm²
- Conductor cross-section (AWG/KCMIL): 8
- Conductor diameter: 3.776 mm
- Nominal insulation thickness: 1.14 mm
- Ground Conductor cross-section (AWG): 14
- Minimum Insulation thickness of ground cable: 0.68 mm
- Nominal outer diameter: 19.77 mm
- Approximate weight: 663.85 kg/km
- Max. DC resistance of the conductor at 20°C: 2.19 Ohm/km
- Ampacity: 55.0 A
- Minimum repeated bending diameter: 237 mm
3x10+3x14AWG
Nexans ref. 209066
- Conductor cross-section: 5.26 mm²
- Conductor cross-section (AWG/KCMIL): 10
- Conductor diameter: 3.048 mm
- Nominal insulation thickness: 0.76 mm
- Ground Conductor cross-section (AWG): 14
- Minimum Insulation thickness of ground cable: 0.68 mm
- Nominal outer diameter: 18.14 mm
- Approximate weight: 535.99 kg/km
- Max. DC resistance of the conductor at 20°C: 3.34 Ohm/km
- Ampacity: 40.0 A
- Minimum repeated bending diameter: 218 mm
3x12+3x18AWG
Nexans ref. 208226
- Conductor cross-section: 3.31 mm²
- Conductor cross-section (AWG/KCMIL): 12
- Conductor diameter: 2.429 mm
- Nominal insulation thickness: 0.76 mm
- Ground Conductor cross-section (AWG): 18
- Minimum Insulation thickness of ground cable: 0.58 mm
- Nominal outer diameter: 15.43 mm
- Approximate weight: 365.75 kg/km
- Max. DC resistance of the conductor at 20°C: 5.31 Ohm/km
- Ampacity: 30.0 A
- Minimum repeated bending diameter: 185 mm
3x14+3x18AWG
Nexans ref. 209065
- Conductor cross-section: 2.08 mm²
- Conductor cross-section (AWG/KCMIL): 14
- Conductor diameter: 1.958 mm
- Nominal insulation thickness: 0.76 mm
- Ground Conductor cross-section (AWG): 18
- Minimum Insulation thickness of ground cable: 0.58 mm
- Nominal outer diameter: 14.92 mm
- Approximate weight: 323.75 kg/km
- Max. DC resistance of the conductor at 20°C: 8.44 Ohm/km
- Ampacity: 25.0 A
- Minimum repeated bending diameter: 179 mm
Description
Description
Standards
-
ProductASTM B 172; ASTM B 174; ASTM B 3; ICEA S-73-532; ICEA S-95-658
Application
CENTELSA by Nexans VFD Cables are specially engineered to provide 100% containment of EMI emissions and provide longer cable life in harsh operating conditions. Are part of a power control system, which mixes the electrical control of industrial machines with electronic automated systems where the main device is a variable frequency drive (VFD), which for industry is basically a variable speed control of electric motors.
These VFD cables feature symmetrical ground conductors that reduce induced voltage imbalances and carry common mode noise back to the drive.
Construction
Phase and ground conductors
Composed of flexible soft copper conductors.
Phase and ground Insulation
Thermosetting compound in cross-linked polyethylene (XLPE), flame retardant (FR), resistant to abrasion, heat and humidity. Compound free of hazardous substances (RoHS).
Conformation
Three insulated phase conductors plus three insulated ground conductors are symmetrically placed between the phase gaps in order to reduce induced voltage imbalances and transport common mode noise back to the drive.
Inner Jacket
Application of jacket over assembly in order to give circularity to the cable.
Shielding
Bare copper tape applied helically with an overlap in order to guarantee 100% coverage.
Overall Jacket
External cover with thermoplastic compound in polyvinyl chloride (PVC), flame retardant, resistant to abrasion, moisture, for use in trays (TC), sunlight resistant (SR). Compound free of hazardous substances (RoHS).
Applicable Standards
- ICEA S-73-532 "Multi-conductor Control Cables"
- ICEA S-95-658 "Multi-conductor Power Cables"
Certificate:
- CIDET N° 06404
- CIDET N° 00408
Operating Temperature
90 °C.
Operating Voltage
600 V
Identification
- Conductors identification:
Three Phase conductors: Black base color plus printed numbers
Three ground conductors: Green base color
- Jacket identification:
Black color with marking and sequential meter by meter.
Packaging Unit
Reels by 500 o 1000 m.
Optional:
- Low-smoke (LS) or halogen-free (HF FR) insulation.
- Low smoke emission (LS) and halogen-free (HF) jacket.
- Operating voltage 2000 V
Ampacity Conditions
- Ampacity to 90°C conductor temperature, 30°C ambient temperature.
- Not more than three current carrying conductors in duct or direct burial. NTC 2050, Table 310.15(B)(16).
NOTE:
- The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
- Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania