Medium Voltage Aluminum 90°C XLPE 8.7/15kV N=25mm2 PVC
Medium Voltage Aluminum 90°C XLPE 8.7/15kV N=25mm2 PVC
Medium Voltage Aluminum Power Cable meets all the requirements of the IEC 60502-2 Standard.
Read more70 mm2
Nexans ref. 207335
- Total number of wires: 19
- Conductor cross-section: 70 mm²
- Conductor diameter: 9.58 mm
- Nominal outer diameter: 25.56 mm
- Approximate weight: 822.36 kg/km
- Minimum outer sheath thickness: 1.24 mm
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.563 Ohm/km
- Nominal capacitance: 225.87 pF/m
- Perm current rating in air 30°C: 230 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 186 A
- Phase reactance 60 Hz - flat formation: 0.165 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.147 Ohm/km
- Maximum Pull Tension of Conductor: 4 kN
- Minimum repeated bending diameter: 307 mm
95 mm2
Nexans ref. 212438
- Total number of wires: 19
- Conductor cross-section: 95 mm²
- Conductor diameter: 11.29 mm
- Nominal outer diameter: 27.43 mm
- Approximate weight: 942.03 kg/km
- Minimum outer sheath thickness: 1.32 mm
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.407 Ohm/km
- Nominal capacitance: 253.16 pF/m
- Perm current rating in air 30°C: 280 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 221 A
- Phase reactance 60 Hz - flat formation: 0.158 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.14 Ohm/km
- Maximum Pull Tension of Conductor: 5 kN
- Minimum repeated bending diameter: 330 mm
120 mm2
Nexans ref.
- Total number of wires: 37
- Conductor cross-section: 120 mm²
- Conductor diameter: 12.81 mm
- Nominal outer diameter: 29.11 mm
- Approximate weight: 1053 kg/km
- Minimum outer sheath thickness: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.322 Ohm/km
- Nominal capacitance: 277.31 pF/m
- Perm current rating in air 30°C: 324 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 252 A
- Phase reactance 60 Hz - flat formation: 0.151 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.134 Ohm/km
- Maximum Pull Tension of Conductor: 6 kN
- Minimum repeated bending diameter: 350 mm
185 mm2
Nexans ref. 207712
- Total number of wires: 37
- Conductor cross-section: 185 mm²
- Conductor diameter: 15.92 mm
- Nominal outer diameter: 32.38 mm
- Approximate weight: 1310.69 kg/km
- Minimum outer sheath thickness: 1.48 mm
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.209 Ohm/km
- Nominal capacitance: 326.51 pF/m
- Perm current rating in air 30°C: 424 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 317 A
- Phase reactance 60 Hz - flat formation: 0.143 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.126 Ohm/km
- Maximum Pull Tension of Conductor: 10 kN
- Minimum repeated bending diameter: 389 mm
240 mm2
Nexans ref. 207695
- Total number of wires: 37
- Conductor cross-section: 240 mm²
- Conductor diameter: 18.25 mm
- Nominal outer diameter: 34.71 mm
- Approximate weight: 1520.59 kg/km
- Minimum outer sheath thickness: 1.48 mm
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- Max. Electrical Resistance AC 60Hz 90°C: 0.16 Ohm/km
- Nominal capacitance: 363.23 pF/m
- Perm current rating in air 30°C: 502 A
- Permissible current rating buried/duct 20°C - Trefoil formation: 367 A
- Phase reactance 60 Hz - flat formation: 0.138 Ohm/km
- Phase reactance 60 Hz - trefoil formation: 0.121 Ohm/km
- Maximum Pull Tension of Conductor: 12 kN
- Minimum repeated bending diameter: 417 mm
Description
Description
Standards
-
ProductIEC 60228 Class 2 ; IEC 60502-2
Application
Medium Voltage single core cables are used in electrical energy distribution networks, as feeders for transformers in substations, industrial facilities and urbanizations. They are suitable for installations in dry or wet locations, outdoors, underground ducts or directly buried in earth.
Construction
1. Conductor: Aluminum, compacted class 2 stranding..
2. Conductor screen: Extruded semiconductive compound.
3. Insulation: Cross-linked Polyethylene (XLPE).
4. Insulation screen: Strippable semiconductive compund.
These last three components extruded in CV (continuous vulcanization) of triple extrusion in the dry curing process.
5. Screen: Made up of round copper wires with a total cross section equal to twenty-five square milimeter, with a non-hygroscopic separator tape over the wires.
6. Outer jacket: PVC compound, flame retardant, resistant to heat, abrasion and humidity, resistant to sunlight (SR), black color.
Applicable Standards
- IEC 60228
- IEC 60502-2.
Certificate
RETIE N° 06418
Operating Temperature
90 °C
Operating Voltage
8.7/15(17.5) kV
Identification
Insulation in natural color and black external jacket. Sequential length meter by meter with return to zero.
Unit Packaging
500 m or 1000 m reels. Other packaging units available upon request.
Optional Features available upon request:
Insulation in XLPE-TR (Tree retardant) compound. External covering in Polyethylene compound. Application of additives for protection against rodents and termites. Water blocking system in conductor and/or screen, longitudinal and/or radial.
For more information, contact our sales representative.
Ampacity and Reactance Conditions
- Ampacities of Three Single-Insulated Aluminum Conductors in Air Based on Conductor Temperatures of 90° C and Ambient Air Temperature of 30°C, trefoil configuration. According to IEC 60502-2, Table B.3.
- Ampacities of Three Single-Insulated Aluminum Conductors Buried direct in the ground, Based on Ambient Earth Temperature of 20°C, Depth of layin of 0.8 m, Thermal resistivity of soil 1.5 K.m/W, Conductor Temperatures of 90°C, screens bonded at both ends According to IEC 60502-2, Table B.3.
- Inductive Reactance to 90°C, 60Hz, 3 conductors spaced 1 diameter. Trifoil and flat configuration.
NOTE:
- The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
- Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantitie.
RECOMMENDATIONS FOR THE SELECTION OF ACCESSORIES AND DUCTS
The technical information presented here is for reference purposes only. Actual dimensions and construction details will only be available with the test reports for each manufacturing order. For the selection of accessories and/or ducts, it is recommended to measure directly on the actual dimensions of the cable using the appropriate methods and instruments. Centelsa by Nexans will not assume any responsibility for the selection of such elements.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania