AWM FLEXIBLE CABLE 600V 105°C PVC RoHS

Products

10 AWG

Nexans ref. 201641

  • Approximate weight: 60.51 kg/km
  • Conductor cross-section: 5.26 mm²
  • Conductor diameter: 3.048 mm
  • Nominal outer diameter: 4.65 mm
  • Ampacity: 28.0 A
  • Max. DC resistance of the conductor at 20°C: 3.41 Ohm/km

 

12 AWG

Nexans ref. 201640

  • Approximate weight: 41.06 kg/km
  • Conductor cross-section: 3.31 mm²
  • Conductor diameter: 2.429 mm
  • Nominal outer diameter: 4.03 mm
  • Ampacity: 23.0 A
  • Max. DC resistance of the conductor at 20°C: 5.42 Ohm/km

 

14 AWG

Nexans ref. 201639

  • Approximate weight: 28.69 kg/km
  • Conductor cross-section: 2.08 mm²
  • Conductor diameter: 1.958 mm
  • Nominal outer diameter: 3.56 mm
  • Ampacity: 17.0 A
  • Max. DC resistance of the conductor at 20°C: 8.61 Ohm/km

 

16 AWG

Nexans ref. 201638

  • Approximate weight: 20.01 kg/km
  • Conductor cross-section: 1.31 mm²
  • Conductor diameter: 1.534 mm
  • Nominal outer diameter: 3.14 mm
  • Ampacity: 8.0 A
  • Max. DC resistance of the conductor at 20°C: 13.7 Ohm/km

 

18 AWG

Nexans ref. 201636

  • Approximate weight: 14.46 kg/km
  • Conductor cross-section: 0.821 mm²
  • Conductor diameter: 1.214 mm
  • Nominal outer diameter: 2.81 mm
  • Ampacity: 6.0 A
  • Max. DC resistance of the conductor at 20°C: 21.9 Ohm/km

 

20 AWG

Nexans ref. 201635

  • Approximate weight: 11.59 kg/km
  • Conductor cross-section: 0.517 mm²
  • Conductor diameter: 1.016 mm
  • Nominal outer diameter: 2.62 mm
  • Ampacity: 4.7 A
  • Max. DC resistance of the conductor at 20°C: 34.7 Ohm/km

 

Description

Description

Standards

  • Product
    UL 758

Application

AWM FLEXIBLE cables are used to connect lighting fixtures, appliance or equipment wiring, and in applications with temperatures up to 105°C. 

Construction

Conductor

Flexible soft copper.

Insulation

Polyvinyl chloride (PVC), flame retardant (FR), resistant to heat, abrasion and humidity; free of hazardous substances (RoHS).

Applicable Standards

UL 758

Certificate

RETIE N° 02703

Operating Temperature

105°C

Operating Voltage

600V

Identification

Insulation in colors according to manufacturing standard.

Ampacity Conditions

  • Ampacity value according to NTC 2050, Table 402.5.
  • 20 AWG: Ampacity value for reference only.

NOTE:

  • The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Flexible
Conductor material
Soft copper
Conductor shape
Bunched Wires
Insulation
PVC

Dimensional characteristics

Dimensional characteristics

Nominal insulation thickness
0.76 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Operating voltage
600 V

Mechanical characteristics

Mechanical characteristics

Abrasion resistance
Good

Usage characteristics

Usage characteristics

Max. conductor temperature in service
105 °C
RoHS compliant
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close