2/0 AWG
2/0 AWG
Flexible soft copper conductor, with thermoplastic elastomer compound (TPE) insulation.
Read more- Nexans ref. : 201509
Description
Description
WELDING CABLES 600V TPE 105°C
Welding cables are used for extra-heavy duty and as power to the electrode of welding equipment, both in alternating and direct current. They are also used in continuous service applications where flexibility is required in installation and/or operation.
Construction
Conductor
Flexible soft copper.
Insulation
Thermoplastic elastomer compound (TPE), flame retardant (FR), resistant to heat, abrasion and humidity; free of hazardous substances (RoHS).
Applicable Standards
NTC 6078
Certificate
RETIE N° 06628
Operating Temperature
105°C
Operating Voltage
600 V
Marking
CENTELSA by NEXANS CABLE DE SOLDADURA Cu 105°C < Calibre AWG / Kcmil > 600 V TPE - HECHO EN COLOMBIA.
Identification
Insulation in black color.
Ampacity Conditions
- Ampacity 1: To 90 °C conductor temperature, 30°C ambient temperature and a load factor of 100%. According to NTC 6078, Table B.5, Up to three current-carrying conductors in a conduit or directly buried.
- Ampacity 2: To 90 °C conductor temperature, 30°C ambient temperature and a load factor of 85%. According to NTC 6078, Table B.4, based on repeated 5-minute work cycles.
NOTE:
- The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
- Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Flexible
Conductor material
Soft copper
Conductor shape
Bunched Wires
Insulation
TPE
Dimensional characteristics
Dimensional characteristics
Approximate weight
683.33 kg/km
Conductor cross-section
67.4 mm²
Conductor diameter
10.83 mm
Nominal insulation thickness
2.03 mm
Nominal outer diameter
14.92 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Ampacity
195.0 A
Ampacity 90°C
357 A
Max. DC resistance of the conductor at 20°C
0.276 Ohm/km
Operating voltage
600 V
Mechanical characteristics
Mechanical characteristics
Abrasion resistance
Good
Mechanical resistance to impacts
UL 493
Usage characteristics
Usage characteristics
Flame retardant
NTC 3203 N°1080, VW-1 Flame Test
Max. conductor temperature in service
105 °C
RoHS compliant
Yes