- Markets
- Catalogue
- Services and solutions
- Company
- Newsroom
- Tools & Resources
- Documents
- Nexans Insights
- Search
- Contact us
- Compare
- Sign in
CABLES AL S8000 THHN/THWN-2 RoHS
CABLES AL S8000 THHN/THWN-2 RoHS
Aluminum conductor S8000, PVC insulation and Nylon jacket.
Read more500 kcmil
Nexans ref. 206654
- Conductor diameter: 18.69 mm
- Nominal insulation thickness: 1.52 mm
- Conductor cross-section: 253 mm²
- Approximate weight: 845.1 kg/km
- Nominal outer diameter: 22.37 mm
- Max. DC resistance of the conductor at 20°C: 0.116 Ohm/km
- Ampacity: 350.0 A
400 kcmil
Nexans ref. 206653
- Conductor diameter: 16.74 mm
- Nominal insulation thickness: 1.52 mm
- Conductor cross-section: 203 mm²
- Approximate weight: 692.55 kg/km
- Nominal outer diameter: 20.42 mm
- Max. DC resistance of the conductor at 20°C: 0.145 Ohm/km
- Ampacity: 305.0 A
350 kcmil
Nexans ref. 206640
- Conductor diameter: 15.65 mm
- Nominal insulation thickness: 1.52 mm
- Conductor cross-section: 177 mm²
- Approximate weight: 615.38 kg/km
- Nominal outer diameter: 19.33 mm
- Max. DC resistance of the conductor at 20°C: 0.166 Ohm/km
- Ampacity: 280.0 A
250 kcmil
Nexans ref. 206639
- Conductor diameter: 13.21 mm
- Nominal insulation thickness: 1.52 mm
- Conductor cross-section: 127 mm²
- Approximate weight: 459.04 kg/km
- Nominal outer diameter: 16.89 mm
- Max. DC resistance of the conductor at 20°C: 0.232 Ohm/km
- Ampacity: 230.0 A
4/0 AWG
Nexans ref. 206638
- Conductor diameter: 12.07 mm
- Nominal insulation thickness: 1.27 mm
- Conductor cross-section: 107 mm²
- Approximate weight: 379.65 kg/km
- Nominal outer diameter: 15.17 mm
- Max. DC resistance of the conductor at 20°C: 0.274 Ohm/km
- Ampacity: 205.0 A
2/0 AWG
Nexans ref. 206636
- Conductor diameter: 9.55 mm
- Nominal insulation thickness: 1.27 mm
- Conductor cross-section: 67.4 mm²
- Approximate weight: 255.02 kg/km
- Nominal outer diameter: 12.65 mm
- Max. DC resistance of the conductor at 20°C: 0.436 Ohm/km
- Ampacity: 150.0 A
1/0 AWG
Nexans ref. 206635
- Conductor diameter: 8.53 mm
- Nominal insulation thickness: 1.27 mm
- Conductor cross-section: 53.5 mm²
- Approximate weight: 210.5 kg/km
- Nominal outer diameter: 11.63 mm
- Max. DC resistance of the conductor at 20°C: 0.55 Ohm/km
- Ampacity: 135.0 A
2 AWG
Nexans ref. 206633
- Conductor diameter: 6.81 mm
- Nominal insulation thickness: 1.02 mm
- Conductor cross-section: 33.6 mm²
- Approximate weight: 135.48 kg/km
- Nominal outer diameter: 9.33 mm
- Max. DC resistance of the conductor at 20°C: 0.875 Ohm/km
- Ampacity: 100.0 A
4 AWG
Nexans ref. 206632
- Conductor diameter: 5.41 mm
- Nominal insulation thickness: 1.02 mm
- Conductor cross-section: 21.2 mm²
- Approximate weight: 93.5 kg/km
- Nominal outer diameter: 7.93 mm
- Max. DC resistance of the conductor at 20°C: 1.39 Ohm/km
- Ampacity: 75.0 A
6 AWG
Nexans ref. 206461
- Conductor diameter: 4.29 mm
- Nominal insulation thickness: 0.76 mm
- Conductor cross-section: 13.3 mm²
- Approximate weight: 57.97 kg/km
- Nominal outer diameter: 6.23 mm
- Max. DC resistance of the conductor at 20°C: 2.21 Ohm/km
- Ampacity: 55.0 A
Description
Description
Standards
-
ProductASTM B 800; ASTM B 801; UL 83
-
NationalNTC 1332; NTC 5535; NTC 5536
Application
THHN/THWN-2 cables are used for electrical wiring in buildings, in power circuits, in industrial, commercial and residential branch and secondary indoor networks.
Special for installations in abrasive places or contaminated with oil, grease, gasoline and other chemical substances.
They are suitable for installation in ducts, pipes, boards and trays according to the RETIE (REGLAMENTO TÉCNICO DE INSTALACIONES ELÉCTRICAS), article 20.3, literal J, from 12 AWG size.
Construction
Conductor
Aluminum conductor S8000.
Insulation
Polyvinyl chloride (PVC), flame retardant (FR), resistant to heat, abrasion and moisture, sunlight resistant (SR) in black color, free of hazardous substances (RoHS).
Jacket
External Jacket in nylon, gasoline and oils resistant (GR II).
Applicable Standards
UL 83, NTC 1332.
Certificate
RETIE No 00406
Operation Temperature
90°C
Operation Voltage
600 V.
Identification
Insulation in black color according to the manufacturing standard.
Ampacity Conditions
- Current capacity for 90°C conductor temperature, 30°C ambient temperature. No more than three current-carrying conductors in a conduit or raceway. NTC 2050, Table 310.15(B)(16)
- The data indicated in this table are subject to normal manufacturing tolerances.
NOTE:
- Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania